Menu 04 – Enable T.A. contact (only active if room probe enabled on external remote control)
4.
Enables Room Thermostat contact functioning if room probe on external remote control is activated
Functioning of Room Thermostat contact is always active if room probe on external remote control is not enabled.
Example:
In this condition...
...if wanting to control boiler with KLOVER remote control room temperature only, I must:
enable room probe on remote control (stove settings menu +> Enable room probe -> ON)
disable boiler thermostat contact on boiler display (menu 4 enable contact -> OFF)
In this case, the boiler firstly enters functioning economy and then automatically switches off when room temperature (detected with KLOVER remote
control) is satisfied.
...if wanting to control boiler with KLOVER remote control room temperature and with boiler thermostat, I must:
enable room probe on remote control (stove settings menu +> Enable room probe -> ON)
enable boiler thermostat contact on boiler display (menu 4 enable contact -> ON)
In this case, the boiler firstly enters functioning economy and then automatically switches off when both temperatures are satisfied.
...if wanting to control boiler with boiler temperature only, I must:
disable room probe on remote control (stove settings menu +> Enable room probe -> OFF). The room probe is automatically disabled if external
remote control is not connected.
enable or disable boiler thermostat contact on boiler display (menu 4 enable contact -> ON/OFF)
In this case, the boiler firstly enters functioning economy and then automatically switches off when boiler temperature (detected with external thermostat
immersed in boiler) is satisfied. This may be a good solution to heat DHW during the summer period.
...if not wanting to control boiler with external thermostats but with heating system water temperature only, I must:
disable room probe on remote control (stove settings menu +> Enable room probe -> OFF). The room probe is automatically disabled if external
remote control is not connected.
enable or disable boiler thermostat contact on boiler display (menu 4 enable contact -> ON/OFF). The contact must be bridged (done in factory).
Only upon reaching of temperature set in "SET H2O" or "SET DHW" does the boiler enter functioning economy.
Summary:
CASE
REMOTE CONTROL ROOM PROBE
1
OFF
2
OFF
3
ON
4
ON
ROOM THERMOSTAT CONTACT
OFF
ON
OFF
ON
17
.
ACTION
Works with room thermostat contact
Works with room thermostat contact
Works with remote control room probe only
Works with remote control room probe and room thermostat
contact