18.3 CHECKING THE BURNER
The burner needs no cleaning.
• Check the burner surface for damage, replace the burner if necessary.
• Check the positioning of the flame detection probe.
• Verify that the distance of the ignition electrode is within tolerance as shown in the figure.
•
Check that the insulation of the burner flange it is not damaged otherwise replace it.
a
Flame detection probe
b
Ignition electrode
c
Burner
d
Burner surface insulation
18.4 COMBUSTION PARAMETERS
To measure combustion efficiency and the emissions of the products of combustion, the boiler is
fitted with two dedicated test points. One connection point is connected to the flue gas discharge
circuit ( A), and allows monitoring of the quality of the combustion products and the combustion
efficiency. The other is connected to the combustion air intake circuit ( B), allowing checking of any
recycling of the combustion products in case of coaxial pipelines. The following parameters can be
measured at the connection point on the flue gas circuit:
• temperature of the combustion products;
• oxygen (
) or carbon dioxide (
• carbon monoxide (
) concentration.
The temperature of the combustion air must be measured on the test point located on the air intake flue (B) by inserting the
measurement sensor by about 80 mm (C).
To enable the " CHIMNEY SWEEP MODE" consult section 12.3.