7. PROBE CHART

The equipment temperature probes are NTC 10 KΩ type, the resistance probe in function of the tempera-
ture is given by the following graphic:

8. TABLE OF ERRORS

The installation, assembly and repair of the equipment can only be carried out by qualified technicians.
Code
Very cold temperature in the thermal accu-
AL
mulator (T_water < 5°C).
Very high temperature in the thermal accu-
AH
mulator (T_water > 80°C).
Water temperature probe in the thermal ac-
cumulator damaged.
Solution:
Verify the integrity of the probe's con-
Pr1
nections on the controller;
Measure
10KΩ, resistance at 25°C equals ±
10KΩ);
Substitute the probe;
Water temperature probe in the thermal ac-
cumulator damaged;
Solution:
Verify the integrity of the probe's con-
Pr2
nections on the controller;
Measure
10KΩ, resistance at 25°C equals ±
10KΩ);
Substitute the probe;
52
Description
probe's resistance (NTC
probe's resistance (NTC
Technical Manual
Problem / Checking
Equipment keeps the regular function.
Equipment keeps the regular function.
Security thermostat turns off the equipment
(rearming the thermostat is handmade)
Equipment continues regular function.
All the active outputs actives are deactivat-
ed (compressor, resistance and ventilator)