...G (R6)...
0.5...0.6 N·m (0.4 lbf·ft)
8
6
5
1.7 N·m
(1.2 lbf·ft)
...G (R8)...
0.5...0.6 N·m (0.4 lbf·ft)
8
5
6
6
4
1.7 N·m
(1.2 lbf·ft)
...G
1...10 kohm
max.
500 ohm
6
6
4
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
Wire sizes: 0.14...2.5 mm
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
X1
Reference voltage and analog inputs and outputs
1
SCR
Signal cable shield (screen)
2
AI1
Output frequency/speed reference: 0...10 V
3
AGND
Analog input circuit common
4
+10V
Reference voltage 10 V DC
5
AI2
Actual feedback: 0...10 V
6
AGND
Analog input circuit common
7
AO1
Output frequency: 0...10 V
8
AO2
Output current: 0...20 mA
9
AGND
Analog output circuit common
X2 & X3
Aux. voltage output and programmable digital inputs
10
+24V
Aux. voltage output +24 V DC, max. 250 mA
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Stop (0) / Start (1)
14
DI2
Not configured
15
DI3
Constant frequency/speed selection
16
DI4
Not configured
17
DI5
Not configured
18
DI6
Not configured
X6, X7, X8 Relay outputs
19
RO1C
Ready run
20
RO1A
250 V AC / 30 V DC
2 A
21
RO1B
22
RO2C
Running
23
RO2A
250 V AC / 30 V DC
2 A
24
RO2B
25
RO3C
Fault (-1)
26
RO3A
250 V AC / 30 V DC
27
RO3B
2 A
X5
Embedded fieldbus
29
B+
30
A-
Embedded fieldbus, EFB (EIA-485)
31
DGND
S4
TERM
Termination switch
S5
BIAS
Bias resistors switch
X4
Safe torque off
34
OUT1
35
OUT2
Safe torque off. Factory connection. Both circuits
36
SGND
must be closed for the drive to start.
37
IN1
38
IN2
X10
24 V AC/DC
40
24 V AC/DC+ in Ext. 24V AC/DC input to power up the control unit
when the main supply is disconnected.
41
24 V AC/DC- in
2
(26...14 AWG): All terminals