Descargar Imprimir esta página

Service ­ Maintenance - Ecoflam MAX GAS PR Serie Manual De Uso

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 42
Service
­ Maintenance
Burner and boiler servicing must only
be carried out by qualified personell.
The system operator is advised to take
out a service contract to guarantee
regular servicing.
The operator is obliged to use the
equipment necessary during mainte­
nance.
1
4
7 7
420010334907
Attention
WARNING
• Disconnect the electrical supply
before carrying out any
maintenance or cleaning work.
DANGER
• The blast tube and firing head
may be hot.
Checking the exhaust gas temperature
• Check the flue gas temperature at
regular intervals.
• Clean the boiler if the flue gas
temperature is more than 30°C above
2
5
7
8
the value measured at the time of
commissioning.
• To simplify the check, use a flue gas
temperature indicator.
Once the maintenance, cleaning
or checking operations have been
completed, reassemble the cover
and all the safety and protection devi­
ces of the burner.
Removing firing head
• See pictures in the order.
3
6
9
www.ecoflam­burners.com
EN
15

Publicidad

loading

Este manual también es adecuado para:

Max gas 350 prMax gas 500 prMax gas 700 pr