Status Indicator - MicroPower Access BMU Basic Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 47

Status indicator

Status indicator on the control panel.
See Access™ BMU.
Indica-
Status
Cause
tion
The battery is too warm.
Flashes
a. Low electrolyte level.
b. The electrolyte level and battery
Flashes
Not used.
Time and date set incorrectly.
Flashes
Time and date are set correctly, unit
Lit
works.
The battery monitoring unit is
searching for a network to connect to
Flashes
or has connection permitted enabled.
Lit
The unit is connected to a network.
All indicators
An identification request has been
flashing
sent from the Access™ Service tool.
No supply voltage.
No indicators lit
These
are lit,
Software in Access™ BMU is being
the
updated.
others
are off.
temperature sensor is installed
incorrectly.
Action
a. Allow the battery to cool.
b. Reduce the workload on the battery.
c. In Access™ Service tool: Check that the battery's
temperature level for alarm indication corresponds
with the battery manufacturer's recommendation.
a. Top up the battery water.
b. Check the installation of the electrolyte level and
battery temperature sensor, see Installation step 3.
Set the time and date with the Access™ Service tool.
Take away the magnet from the magnetic switch.
The indicators go out automatically after the requested
identification time has elapsed, normally 10 seconds.
Check the battery monitoring unit's connections to the
battery's positive terminal.
Check the fuse on the cable between the battery
monitoring unit and the battery's positive terminal.
Wait until Access™ BMU starts up, this normally takes
15-30 seconds. Do not disconnect the supply voltage.
7