Installation
DANGER -RISK OF ELECTRIC SHOCK-DISCONNECT POWER TO LIGHT FIXTURE BEFORE INSTALLATION.
To replace uorescent tube lamp with LED tube lamp, the wiring must be installed according to these instructions to
ensure a complete and safe installation of the LED tube lamp.
Integral LED Tube Lamp Wiring Diagram
Black
120-277~
White
Note: LED Tube Lamp requires single end power only; wiring to one side of the xture is suf cient. Ensure lamp end
labeled "POWER THIS END" is installed to the live circuit.
CAUTION: LAMP HOLDERS MUST BE NON-SHUNTED. POWER FLOWS THROUGH LED TUBE LAMP
1. Turn off the power to the light xture at the breaker panel before installation.
2 If retro tting an enclosed xture open the diffuser from the light xture.
3. Remove existing uorescent lamps. Please dispose or recycle these items properly in accordance with local
requirements as they contain mercury.
4. Open the wiring cover to expose the uorescent ballast.
Ballast
Inductive ballast type
Black
Ballast with 2 lamps