4.4 Disassembly of Compressor Feet
In order to prevent unit from damage during transportation, 2 metal pieces are fitted to outdoor unit's
compressor feet before unit leaves factory. See fig.19.
When installing the unit, metal pieces for transportation must be removed. Then fasten the binding nuts
again and wrap back soundproofing cotton.
NOTE!
If unit runs with metal pieces fitting on, compressor will shake abnormally and unit's operating life will
be shortened.
4.5 Vacuum Pumping, Refrigerant Adding

4.5.1 Vacuum Pumping

(1) Outdoor unit has been charged with refrigerant before delivery. Field-installed connection pipe needs
to be charged with additional quantity of refrigerant.
(2) Confirm whether outdoor liquid and gas valves are closed.
(3) Use vacuum pump to withdraw the air inside indoor unit, hydro box, hot water converter and
connection pipe from the outdoor valve, as shown below.