9.2.2 Enable / Disable
This feature allows each input to be either Enabled or Disabled. When Disabled there
will be no messages reported on the "List Status Events" log even if there is a toggle on
the input. Note that by default all inputs are set to Enabled.
9.2.3 Current Status
A read only function that shows the current status of the input when the "Read
parameters" button is pressed.
9.2.4 Normal State
Defines whether the normal state of the input is OPEN or CLOSE. OPEN represents a
potential difference between both terminals of the input, CLOSE represents a short
between both terminals of the input.
9.2.5 Event Count
Every time that a toggle occurs on the input, the Event Count number is increased by
1. The increment also occurs if the input is disabled. When the "Read parameters" is
pressed, the Event Count field is updated with the count number. The user can also
use this field to write any number, which means the count can be reset by entering the
value 0.
9.2.6 Count Threshold
The Count Threshold is the required number of toggles (Event Count) on the input
before a message is reported on the "List Status Events" log. For example if the Count
Threshold of input 03 is 1000, the Connex-02 will only report a message on the "List
Status Events" log once the value of "Event Count" reaches 1000.
9.3 Outputs
The 2 outputs are identical and can be configured the same way.
13