BTL7-A/E1 _ 0-M _ _ _ _ -K(8)-SA262-K _ _ /F _ _
Micropulse Transducer - Rod Style

Electrical connection

Cable color
-A100
YE yellow
Not used 1)
GY gray
PK pink
GN green
0...10 V
WH white
BU blue
BN brown
RD red 3)
Shielding and cable routing
Defined ground!
The transducer and the control cabinet must be
at the same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect the transducer and controller using a shielded
cable.
Shielding: Copper filament braided, at least 85%
coverage.
Cable version: On the transducer side, the cable
shielding is connected to the housing.
Ground the cable shielding on the controller side
(connect with the protective earth conductor).
Magnetic fields
The position measuring system is a magnetostrictive
system. It is important to maintain adequate distance
between the transducer cylinder and strong, external
magnetic fields.
Cable routing
Do not route the cable between the transducer, controller,
and power supply near high voltage cables (inductive stray
noise is possible). The cable must be routed tension-free.
Cable length
BTL7-A
Max. 30 m 1)
BTL7-E
Max. 100 m 1)
1) Prerequisite: Construction, shielding and routing preclude the effect of
any external noise fields.
Installation
NOTICE!
Interference in function
Improper installation can compromise the function of the
transducer and result in increased wear.
► The mounting surface of the transducer must make
full contact with the supporting surface.
► The bore must be perfectly sealed (O-ring/flat seal).
www.balluff.com
-A170
-E100
Not used 1)
4...20 mA
0 V
La (programming input)
10...0 V
Not used 1)
Lb (programming input)
GND 2)
20...28 V
Not used 1)
-E170
20...4 mA
Not used 1)
1) Unassigned leads can be connected to GND on the
controller side but not to the shield.
2) Reference potential for supply voltage and EMC-
GND.
3) Not for BTL7-....-SA262-K_ _
To achieve a secure mounting, attach the transducer with
all 6 cylinder head screws (ISO 4762, M6 × 16 - A2-70).
All screws must be tightened to 3.5 Nm.
For horizontal assembly with nominal lengths > 500 mm,
support the rod and tighten it at the end if necessary (only
possible with a diameter of 10.2 mm).
If installed in a hydraulic cylinder, the magnet should not
make contact with the rod. Minimum bore diameter in the
support piston:
Rod diameter
10.2 mm
8 mm
Startup
DANGER
Uncontrolled system movement
When starting up, if the position measuring system is part
of a closed loop system whose parameters have not yet
been set, the system may perform uncontrolled
movements. This could result in personal injury and
equipment damage.
► Persons must keep away from the system's
hazardous zones.
► Startup must be performed only by trained technical
personnel.
► Observe the safety instructions of the equipment or
system manufacturer.
1. Check connections for tightness and correct polarity.
Replace damaged connections.
2. Turn on the system.
3. Check measured values and adjustable parameters
regularly (especially after replacing the transducer or
after repair by the manufacturer). Recalibrate the
transducer, if necessary.
The calibration procedure is described in the
comprehensive user's guide.
Bore diameter
At least 13 mm
At least 11 mm