Dynamic Braking Resistors
WARNING Isolate supply and ensure residual energy is discharged before wiring up the product.
Dynamic Brake Resistors tend to be used when an application requires
regenerated power from the motor to be dissipated.
The AC30 Frames D - K are all fitted with an internal brake switch as
standard, ready for connection to an external Dynamic Brake Resistor.
Wiring Details
Where a Dynamic Brake Resistor (DBR) is required for an inverter
application, connect across the terminals DB+ & DB (Frames D - J), or
across the terminals DC+ & DB (Frame K only).
WARNING
Do not apply external voltage sources (mains supply or
otherwise) to any of the braking terminals: DB+, DB. This can
lead to damage to the drive and installation, and risk to
personnel.
Internal Filter Disconnection
WARNING
Ensure that all wiring is electrically isolated and cannot be made
"live".
Do not touch filter terminals or cabling for at least 3 minutes after
removing the AC or DC supply.
For full instructions on how to disconnect the EMC Filter please refer to
HA503711U001/U002 'Chapter 4: Installation – Power Stack':
Power Ratings
See HA503711U001/U002/U003 'Appendix D: AC30 Series Product Codes' for understanding the product code.
Order Code
380-480Vac (±10%) Three Phase Supply / 510-650Vdc Supply
7 1 0 - 4 D 0 0 0 4 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 D 0 0 0 6 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 D 0 0 1 0 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 D 0 0 1 2 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 E 0 0 1 6 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 E 0 0 2 3 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 F 0 0 3 2 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 F 0 0 3 8 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 F 0 0 4 5 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 G 0 0 4 5 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 G 0 0 6 0 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 G 0 0 7 3 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 H 0 0 8 7 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 H 0 1 0 5 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 H 0 1 4 5 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 J 0 1 8 0 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 J 0 2 0 5 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 J 0 2 6 0 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 K 0 3 1 5 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 K 0 3 8 0 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 K 0 4 4 0 - B 2 - 0 S - 0 0 0 0
7 1 0 - 4 L 0 5 3 0 - N 2 - 0 S - 0 0 0 0
7 1 0 - 4 L 0 5 9 0 - N 2 - 0 S - 0 0 0 0
7 1 0 - 4 M 0 6 5 0 - N 2 - 0 S - 0 0 0 0
7 1 0 - 4 M 0 7 0 0 - N 2 - 0 S - 0 0 0 0
7 1 0 - 4 N 0 7 9 0 - N 2 - 0 S - 0 0 0 0
Normal Duty Ratings
400Vac
460Vac
O/P
O/P
kW
Current
hp
Current
Arms
Arms
1.1
3.5
1.5
3
2.2
5.5
3
4.8
4
10
5
7.6
5.5
12
7.5
11
7.5
16
10
14
11
23
15
21
15
32
20
27
18.5
38
25
36
22
45
30
40
22
45
30
40
30
60
40
52
37
73
50
65
45
87
60
77
55
105
75
96
75
145
100
124
90
180
125
156
110
205
150
180
132
260
200
240
160
315
250
302
200
380
300
361
250
440
350
414
280
530
450
520
315
590
500
590
355
650
550
650
400
700
600
680
450
790
650
770
DB+ DB
DB+ DB
Heavy Duty Ratings
400Vac
460Vac
O/P
O/P
kW
Current
hp
Current
Arms
Arms
0.75
2.5
1
2.1
1.5
4.5
2
3.4
3
7.5
-
-
4
10
5
7.6
5.5
12
7.5
11
7.5
16
10
14
11
23
15
21
15
32
20
27
18.5
38
25
36
18.5
38
25
36
22
45
30
40
30
60
40
52
37
73
50
65
45
87
60
77
55
105
75
96
75
145
100
124
90
180
125
156
110
205
150
180
132
260
200
240
160
315
250
302
200
380
300
361
250
480
400
480
280
530
450
520
315
590
500
590
355
650
550
640
400
700
600
700
English
Frame D - G
DB+ DB DC+ DC-
Frame H
Frame J
Frame K
D
D
D
D
E
E
1
Device Family
F
1
AC Line Fed, IP20
F
4
DC Link Fed, IP20
F
2
EMC Filter
G
N
No filter fitted
G
E
Category C3 filter fitted
G
F
Category C2 filter fitted
H
H
H
J
J
J
K
K
K
L
L
M
M
N
1-9