3 | Specifications
Chemical
SAE recommended
leak test procedure
Always leak test with the engine off.
8 / 357
Ford clear silicon rubber
®
Motorcraft
G-05 antifreeze/coolant
®
Gunk
liquid wrench
Ford pumice/lotion hand cleaner
Ford Motorcraft DOT3 brake fluid
Ford silcon lubricant
®
Dexron
automatic transmission fluid
Mineral engine oil
1.
Charge the system with sufficient refrigerant to have a gauge pressure of at
least 340 kPa (50 psi) with the system off. At ambient temperatures below 15 °C
(59 °F) leaks may not be measurable because the pressure may not be
reached.
2.
Visually trace the entire refrigerant system, and look for signs of air conditioning
lubricant leakage, damage and corrosion on all lines, hoses and components.
Check each questionable area with the detector probe, as well as all fittings,
hose-to-line couplings, refrigerant controls, service valves with caps in place,
brazed or welded areas, and areas around attachment points and hold-downs
on lines and components. If looking for an apparently larger leak, check first at
the medium (7 g/year) or low (14 g/year) sensitivity setting.
3.
Always follow the refrigerant system around in a continuous path so that no
areas of potential leaks are missed. If a leak is found, always continue to test
the remainder of the system.
4.
Recheck the service valves with the caps removed. Blow shop air over the
service valve to clear the immediate area. Check with a detector on the medium
sensitivity setting (7 g/year).
5.
Move the detector at a rate of no more than 75 mm/s (3 in./s) and as close as
possible to 9.5 mm (3/8 in.) from the surface, completely encircling each test
position (switch, sensor, refrigerant tubing connection, etc.).
6.
Slower movement and closer approach of the probe normally improves the
likelihood of finding a leak. However, detectors made to meet this standard are
based on air sampling from the 9.5 mm (3/8 in) distance. A retest is advisable
when a leak appears to be found at the most sensitive settings, particularly if the
False-Trigger
yes
no
no
no
no
no
no
no
074-710-P16A D-TEK 3 Operating Manual