Correct Installation Of Indoor Unit Refrigerant Pipe Work - Saunier Duval SDH 17-050 M2NW Manual De Instalación

Ocultar thumbs Ver también para SDH 17-050 M2NW:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 56
Fig. 9.8
Mounting plate for 17-050 NMWI.
• Case B: Running the pipework out of either side or the
bottom of the unit.
In this case holes do not have to made in the wall since the
indoor unit body has knock outs which can be removed to
allow the pipes to exit the unit: choose the most convenient
one for the desired outlet position (see Figures 9.7).
- Carefully break the knock out in the casing using pliers.
4
3
2
Fig. 9.9
Openings for the installation of the pipes.
Legend
1
Exit for left piping
2
Securing with adhesive tape
3
Exit for indoor piping
4
Exit for right piping
9.3.5
Correct installation of indoor unit
refrigerant pipe work
If installing the rear exiting piping:
• Place a seal ring for the hole in the piping and insert the
coolant pipes with the condensed water pipe through the
hole.
• Remember to seal the hole inside and out properly after
installing the pipes.
• Carefully bend the installation pipe in the right direction,
taking care not to overbend or kink the pipe.
SDH17-MNW-I_EN - 11/14 - Saunier Duval
1
INSTALLATION
EN
- 13 -

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Sdh 17-060 m2nwSdh 17-085 m3nwSdh 17-085 m4nw

Tabla de contenido