CPV..-GE-ASI-8E8E-...
1
User instructions
The AS-Interface valve terminal type 10 is designed exclusively
for controlling pneumatic actuators and may only be used in
bus systems in accordance with the AS-Interface specifications.
The specified limit values for pressures, temperatures, electrical
data, moments, etc. must be observed when additional com-
mercially-available components such as sensors and actuators
are connected.
AS-Interface bus systems and valve terminals may only be in-
stalled by specially qualified personnel. Detailed specifications
on the design and addressing of the bus system can be found
in the manual for the AS-Interface master.
Valve terminal type CPV..-GE-ASI-8E8A-Z uses 2 AS-Interface
addresses. It behaves on the AS-Interface bus like two individ-
ual valve terminals each with 4 inputs and 4 outputs (valve
slots).
Detailed information on the pneumatic components of the valve
terminal can be found in the pneumatics manual P.BE-CPV-.... .
WARNING
• Switch off the power supply before connecting or dis-
connecting plugs (otherwise functioning may be impaired).
• Connect one of the earth/ground connections on the end
plates with low impedance (short cable with large
cross-sectional area) to the earth potential.
PLEASE NOTE
Commission only a valve terminal which is completely fitted
and wired.
9907NH
15