Output module CPX...
continued
Voltage drop at output
Switch−off delay
from 0" to 1"
from 1" to 0"
Parallel switching of outputs
for increased performance
Protection against reverse
voltage
Limiting the inductive
switch−off voltage of
connected coils/solenoid
valves
Electrical isolation
Between the channels
For operating voltage
supply U
EL/SEN
Isolation
Festo CPX−EA 0705c English
−4DA
−8DA
1 V
With ohmic load:
< 200 s
< 200 s
Yes, max. 4 outputs of
the same module:
A0...A3
A0...A3 /
A4...A7
Max. U
OUT
Typical −16 V
none
Yews, when using an intermediate
supply or interlinking block type
CPX−GE−EV−Z (M18),
CPX−GE−EV−S−7/8−5POL,
...−Z−7/8−5POL or ...−Z−7/8−4POL
Tested using 500 V DC
−8DA−H
not per
mitted
27