Connect The Control Cables - ABB ACQ580-01-145A-4 Guía Rápida De Instalación Y Puesta En Marcha

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 31

Connect the control cables

See figure
D
on page 84. It shows an example with one analog signal cable and one
digital signal cable. Make the connections according to the default configuration in
use. The default connections of the Water default configuration are shown in section
Default I/O connections
Example of connecting an analog signal cable:
1. Cut an adequate hole into the rubber grommet and slide the grommet onto the
cable. Slide the cable through a hole of the bottom plate and attach the grommet
to the hole.
2. Ground the stripped outer shield of the cable 360 degrees under the grounding
clamp. Keep the cable otherwise unstripped as close to the terminals of the
control board as possible. For analog signal cables, ground also the pair-cable
shields and grounding wire at the SCR1 terminal. Secure the cables mechanically
at the clamps below the control board.
3. Route the cable as shown in the figure.
4. Connect the conductors to the appropriate terminals of the control board and
tighten to 0.5...0.6 N·m (0.4 lbf·ft).
5. Tie all control cables to the provided cable tie mounts.
6. Put the unused rubber grommets to the holes in the lead-through plate.
EN – R6...R9 Quick installation guide 17
on page 18.
R0-
R4
R6-
R9
R6-
R9
EN
DE
ES
FR
IT
RU
SV
ZH

Publicidad

Tabla de contenido
loading

Tabla de contenido