F12 RALLY
ELECTRICAL CONNECTIONS: TERMINAL BOARDS
1
PEDESTRIAN START input (NO) 11- 12
2
Photocell input (NC)
Common for PEDESTRIAN START
3
and Photocell
4
START input (NO)
5
STOP input (NC)
6
Common for STOP and START
+12 VDC output for accessory power supply.
7 = POSITIVE. CAUTION: to run the
7 - 8
PHOTOTEST the photocell TX must be
connected to terminals 13-14.
9 - 10
+12VDC output for electric lock 15W
FUNCTIONS
The control unit performs the following functions by means of the dip switches:
DIP1
ON
DIP1
OFF
DIP2
ON
DIP2
OFF
DIP3
ON
DIP4
ON
DIP5
ON
DIP6
ON
DIP6
OFF
DIP7
ON
DIP8
ON
DIP9
ON
DIP10
ON
The dip switches must be adjusted when the control unit is not powered.
DEFAULT SETTINGS: Dip 1 – Dip 2 - Dip 4 – Dip 8 - Dip 9 – Dip 10 = OFF
PROGRAMMING
Normal operation
Enables the CONDOMINIUM function. One start command opens and no further start
commands are accepted during opening. During PAUSE one start command reloads the
Pause Time. During CLOSING one start command stops and reopens.
Enables the STEP-BY-STEP function (one start command opens, a second command stops
and a third command closes, the next command stops) or STEP-BY-STEP with AUTOMATIC
RECLOSING depending on how DIP7 is set.
Enables deceleration at the beginning and end of each manoeuvre
Enables pre-flashing of 3 seconds prior to each movement phase
Enables pedestrian opening with the second channel of the TX (only version with built-in receiver)
Photocell input (terminals 2-3) active during both opening and closing. During opening, stops the motion and
opens only when the contact has been freed. During closing, stops and after 1 second inver ts the motion.
Photocell input (terminals 2-3) active only during closing with stop and inversion of motion.
Enables automatic reclosing at the end of the pause time stored (max. 90 seconds).
Enables the WATER HAMMER function which consists of a short closing thrust before
opening to facilitate release of the electric lock
Disables the ANTI-CRUSHING function.
An obstacle found during gate movement is considered as a limit switch.
NOT USED, HOLD IN OFF.
Free relay contact (NO) for light
12VDC output for photocell TX power
13- 14
supply to use to
run the PHOTOTEST (13 = positive)
+12VDC output for flashlight
14- 15
(15 = positive)
Motor 1 output
16- 17
(16 = positive during opening)
Motor 2 output
18- 19
(18 = positive during opening)
20
Antenna ground
21
Antenna signal
F - N
Power supply input 230 VAC 50-60 Hz