Routing Cables And Electrical Connection; Electrical Connection; Replacing The Connection Cable - GEZE Slimchain 230V AC Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 41

Routing cables and electrical connection

6
Routing cables and electrical connection
X
Ensure that the connection to the power supply is only carried out by a
qualified electrician. The main connection must be carried out according
to DIN VDE 0100-600.
X
Use an on-site, 2-pole automatic circuit breaker with locking option,
according to the permissible current carrying capacity of the cable, as the
disconnecting device on the mains side.
X
The details in these instructions must be observed when connecting
components. Planning and calculation of the power network is to be done
by a qualified installer and has to be carried out in accordance with the
statutory regulations (in Germany for example in accordance with MLAR).
X
Before the system is approved for operation, carry out and log an isolation
measurement of the supply network of the system
X
Use only cables prescribed in the wiring diagram. Implement the cable type,
line length and cross-section in accordance with the technical specifications.
X
Always use wire-end ferrules for wire cores.
X
Insulate wires that are not used.
6. 1

Electrical connection

DANGER
Before working on the electrical system interrupt the power supply, secure
it against being switched on again and verify the safe isolation from supply.
6.2

Replacing the connection cable

The connection cable provided (2 m) can be replaced if necessary (e.g. different
cable length, faulty):
à Replacement is only permissible when carried out by a qualified electrician.
Only the same cable type with a temperature range of -5°C .... 80°C, e.g.
GEZE mat. no. 183191 may be used.
EN 8
BU
blue
BN
brown
BK
black
Slimchain 230 V AC
N
CLOSE (230 V AC)
OPEN (230 V AC)

Publicidad

Tabla de contenido
loading

Tabla de contenido