Inspection of installed system

7
Inspection of installed system
à The measures for protection and prevention of crushing, impact, shearing
or drawing-in spots, in particular at points with a height of less than 2.5 m
are to be considered and carried out.
One measure is, for example, to use a switch with an OFF default setting
(for example GEZE vent switch LTA-LSA GEZE mat. no. 118476).
In the case of children or persons with a limited ability to judge, a key-
operated switch with an OFF default setting has to be used (for example
GEZE mat. no. 117996 for SCT, GEZE mat. no. 090176 for cylinder).
The switches must be mounted in such a way that the danger zones can be seen.
X
After installation has been completed, check that the system is set correctly
and is functioning correctly and safely.
X
Check all the functions by carrying out a trial run.
X
The end user has to be instructed in all the important operating and handling
steps after completion.
X
Inform the electrician by handing out this wiring diagram.
X
Cleaning staff must be instructed by the building operator on safe use of
the system and be made aware of the dangers of power-operated windows.
à Windows may only be cleaned from the outside or inside when they are closed.
X
The drive must be protected from construction dirt and splashwater.
8

Commissioning

The first time operating voltage is applied, the drive can be
operated in the "OPEN" and in the "CLOSE" direction. The drive automatically
detects the closing position of the window when closing for the first time and
saves this.
It must be ensured that there is no hindrance at that time.
Should the drive reverse after reaching the closing position (drive opens
by approximately 15 mm), a commissioning run must be started. To do this,
proceed as follows:
X
Open the service cover on the drive housing.
X
Activate push button S1 under the service cover for approx. 3 seconds
(window starts to close).
X
Following the commissioning run, close the service cover again (tightening
torque max. 0.9 Nm).
Push button S1 is only queried with voltage applied and the window at a
standstill.
EN 10