86
Press one of the arrow keys
ing to press down on the arrow key. ProG appears.
Example:
or
. Press ENTER
S1 Switch 1
Upper switching point
Nominal device pressure
Reverse switching point / lower switching point
Nominal device pressure - 10%
Switch function nCLS NC contact/noPn NO contact
noPn Normally open contact
Switch function Hys Hysteresis/Fen Window
Hys Hysteresis (Standard switch)
Delay for upper switching point SP1
00.05 sec (50 ms) attenuation
Delay for lower switching point rSP1
00.05 sec (50 ms) attenuation
S2 Switch 2
Upper switching point
Nominal device pressure
Reverse switching point / lower switching point
Nominal device pressure - 10%
Switch function nCLS NC contact/noPn NO contact
noPn Normally open contact
Switch function Hys Hysteresis/Fen Window
Hys Hysteresis (Standard switch)
Delay for upper switching point SP2
00.05 sec (50 ms) attenuation
Delay for lower switching point rSP2
00.05 sec (50 ms) attenuation
while continu-