Installation Preparation
Indoor Air Flow Data
Indoor air flow may be determined by measuring the
external static pressure (ESP) of the duct system and
then using the chart below to determine the actual
airflow. Under no circumstances should the Zoneline
unit be operated to an ESP in excess of .3" W.C..
Operation of the Zoneline under this condition will result
in inadequate air flow thus leading to poor performance
and/or premature component failure.
ESP
High
(in. water)
CFM
0.1
0.15
0.2
0.25
0.3
0.1
0.15
0.2
0.25
0.3
0.1
0.15
0.2
0.25
0.3
0.1
543
0.15
514
0.2
481
0.25
458
0.3
442
* Do not operate unit in these conditions
NOTE: Values taken at 70-75°F ambient temperature
Your airflow should be balanced based on many
factors, such as available ESP, room CFM, and
ductwork. Consult an HVAC engineer for proper
applications. External static pressure (ESP) can be
measured with a manometer or pitot tube. Once this
ESP is established, you can calculate the CFM using
the above chart.
16
Indoor Fan CFM
Fan Boost Mode
ON
OFF
Medium
Medium
CFM
CFM
468
408
408
435
371
371
409
351
351
392
306
306
352
239
239
468
408
408
435
371
371
409
351
351
392
306
306
352
239
239
468
417
417
435
380
380
409
359
359
392
318
318
352
253
253
468
468
435
435
409
409
392
392
352
352
Indoor Air Flow Data (cont)
AZ95(H/E)09
305 408 468 356 408 468 376 417 468 408 468 543
•
• = Recommended Mid Range
Higher CFMs tend to increase Sensible capacity,
enhance room circulation and increase duct noise,
while lower CFMs tend to increase Latent capacity
and reduce noise.
Ductwork
Low
Prepare the closet ductwork for later connection
CFM
to the case.
305
The duct system should be designed for a maximum
272
friction rate of .30" water column taking into
198
consideration all fittings, registers and/or diffusers.
*
DO NOT operate unit without a supply duct
*
attached.
356
The return air to the Zoneline unit MUST NOT be
ducted, and all units MUST have a free return air
328
configuration to perform properly.
288
The total flow rate (CFM) and external static pressure
220
(ESP) available can be estimated from the charts on
*
this page. Use these charts to select your fan speed
376
setting.
345
The collar on top of the unit accepts standard 10"
314
duct. Pull all duct tight. Extra duct slack can greatly
increase static pressure.
250
*
NOTICE:
408
airflow restrictions. Do not use flex duct for 90°
371
bends or unsupported runs of 5 ft. or more.
351
306
239
CFM Recommendations
AZ95E12
AZ95H12
•
•
Flex duct can collapse and cause
AZ95(H/E)18
•
49-5000561 Rev. 1