Installation
Notes:
•
Installation shall only be performed by qualified personnel and in accordance with
local governing regulations.
•
This product is susceptible to electrostatic shock. Follow proper grounding
procedures.
•
Do not use a Ground Fault Interrupt (G.F.I.) with the SITRANS LR 300. The ground
path is used for filtering purposes in conjunction with the universal power supply.
Mounting Location
Coni
cal
Note:
Mounting: Horn Antennas or Shielded Rod
SITRANS LR 300 Wiring Requirements
•
Increased safety, EEx e version:
•
General safety or hazardous EEx d version: rigid 0.2 to 4
Notes:
•
Recommended torque on terminal clamping screws is 0.5 – 0.6 Nm.
•
Connect shielding of instrument cables to ground at one end only.
7ML19985QA81
P
a
ra
b
o
lic
preferred
acceptable
undesirable
Minimum
10 mm (0.5")
SITRANS LR 300 – QUICK START MANUAL
Fl
at
o
28
o
20
o
12
Minimum
10 mm (0.5")
solid 4
flexible stranded 2.5
flexible stranded 0.2 to 2.5
AWG 24 to 12
100 mm (4") horn antenna
Rod antenna or 150 mm (6")
horn antenna
200 mm (8") horn antenna
Page EN-3