Configuring pins 2 and 5 (optional)
Important: the following information does not apply to Pulsar EX7/10 and Pulsar ESV+
UPSs (pin 2 not used).
Table of possible settings:
Settings
Standard settings:
Battery to be
replaced and
common electrical
reference at 0V.
Customer setting:
Battery to be
replaced and volt-
free contacts.
Customer setting:
Emergency off.
Note: The "emergency off" configuration only works if
pin 5 remains connected to 0 V.
Status information card, user manual
JP01
JP02
Connec-
Connec-
ted
ted
Connec-
Connec-
ted
ted
Removed
Removed
JP03
JP04
Removed
Connec-
ted
Removed
Removed
Connec-
Connec-
ted
ted
External emergency off contact.
5
Comments
Pin 2 delivers the
"battery to be replaced"
signal.
Pin 5 is referenced to 0V.
Pin 2 delivers the
"battery to be replaced"
signal.
Pin 5 is volt-free.
Pins 2 and 5 receive the
customer "emergency off"
command:
S1 wiring, max. length
10 m, see diagram below
(pin 5 remains connected
to 0V).
S1
4
3
2
1
9
8
7 6
5103222900/BB
- 3