3.3 Interface configuration
MODBUS (RTU) Slave configuration
Interface Baud rate Data format Address
RS485
9600
CR/LF Master configuration
Interface Baud rate Data format Address
RS485
9600
Page 4 | ENG
1 Start bit
8 Data bits
1-247
Even Parity
1 Stop bit
1 Start bit
8 Data bits
1-99
No Parity
1Stop bit
3.4 Programming
Main interface programming
menu.
Interface protocols
MODBUS protocol
CR/LF protocol
Slave Address
CR/LF: 1 – 99
MODBUS: 1- 247
Cycle time (only for CR/LF)
0,5 – 9999,9 sec (ON)
0 sec
Data sources (only for CR/LF)
Main counter
Batch counter
Totalizer
Main and batch counter
Main counter and totalizer
The data sources can be set according to the
output operations set for the device. If the
concerned counter shows an overflow / underflow,
it does not send the data value, but +oooooo /
+uuuuuu.
Main menu for programming the
signal and control inputs
User input 1
User input 2
Triggering of the data
transmission via the user input;
possible cycle time ≥ 0, 5 sec
(possible only for CR/LF and
cycle time = 0)
Factory settings are highlighted
in grey.
(OFF)