4.2.3 The Auto Operating Mode
1. The following parameters can be programmed
for the Auto mode:
1 sec
EN - Page 8
A
see 4.2.3.1
to
to
to
to
to
to
2. Functions
SPecial display function, see 4.2.3.1
–
SiGnal allows selecting the setpoint
–
output in volts or mA.
time allows selecting the time unit in
–
seconds or minutes.
Number of PEriods allows defining
–
the number of reference points.
output 1 allows selecting the current
–
or voltage value for the first reference point.
PEriod. 1 allows defining the duration
–
of the first period.
(A maximum of 20 periods may be programmed)
The maximum setpoints ou. X and the times PE.
X result from the setting of PEr.
The function cYcle allows defining
–
the number of cycles to be carried out.
If cYcle = 0,
matically after 1 second. noCYcle will start an
endless loop.
Press both keys simultaneously to switch over to
the following parameter. Within a parameter, select
the decade with the left key and select a value
from 0 ... 9 with the right key.
3. After setting the value of cYcl, press both keys
simultaneously; the following message is dis-
played:
4. Use the right key to select YES or no
⇑
5. If YES is selected, press both keys simulta-
neously to end the programming
⇑
⇑
A
to
bei mA 24.00
to
bei mA 24.00
to
is displayed auto-