MYCOMFORT LARGE
CONFIGURATION OF 0-10V ANALOG
(PARAMETER P14)
The table below is a guide to setting parameter P14 correctly based on the type of
valve(s) and fan the unit is equipped with. For each type of unit an indication is given
of which value should be assigned to parameter P14 and the consequent use mode
of the two analogue outputs.
TYPE OF UNIT
GB
2 or 4 pipes unit with
ON/OFF valve and non-
modulating fan
2 pipes unit with modulating
valve and non-modulating
fan
2 pipes unit with modulating
valve and modulating fan
4 pipes unit with modulating
valves (modulating fan not
allowed)
2 or 4 pipes unit with
ON/OFF valve(s) and
modulating fan

SERIAL COMMUNICATION

Connection to the RS485 communication network
The bus-type communication network consists of a 2-conductor shielded cable
connected directly to the RS485 serial ports of the controls (terminals A, B and GND).
"For the network use a cable AWG 24 (diam. 0.511 mm)"
For more detailed information on the choice of cable, refer to the "Guide to RS485
networks" (RG66007420)
The communication network must have the following general structure (figure 5):
Where:
1
Common = display
2
RS232-RS485 Converter
3
Pull up
4
Pull down
5
Termination
where LT represents the termination resistors at either end of the network.
NB:
(1) Comply with the polarity of the connection: indicated with A(+) and B(-)
(2) Avoid ground loops (ground shield at one end only)
"ERGO" solution (figure 6)
In the case of the "ERGO" solution, the master function is performed by the personal
computer in which the ERGO supervision software is installed. This computer is
connected to the network via an RS232-RS485 converter, which supplies power to
the network itself.
Where:
1
RS232-RS4854 (USB-RS485) converter
If the serial converter provided is used, it will be necessary to connect a termination
resistor (120 ohms) only to the last device of the bus network, since one is already
present in the converter itself.
"SMALL" solution
In the case of the "SMALL" solution a termination resistor will have to be installed on
both controllers at the furthest ends of the network.
FC66002638 - rev. 05
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
OUTPUTS
P14
AOUT1
AOUT2
0
not used
not used
valve
1
modulation
--
valve
fan
2
modulation
modulation
cold water
hot water
valve
valve
3
modulation
modulation
fan
4
--
modulation
SUGGESTED LAYOUT OF NETWORK (figure 7)
Where:
A
RS232-RS4854 Converter
B
Deviations (L<20m)
C
Main branch of network (L < 1000m)
T1 Terminal 1
T2 Terminal 2
T3 Terminal 3
TN Terminal N
WARNING:
> Maximum length of the main branch: 1000 m
> Maximum length of each secondary branch: 20 m
WARNING:
> Use a shielded cable AWG24
WARNING:
> Colours suggested for the communication network: A (+) Color White, B (-) Color
Black
If several levels need to be wired, a SINGLE MAIN BRANCH line must be set up to
guarantee a bus-type network (see figure 8):
Where:
A
1st level main branch
B
2nd level
C
2nd level main branch
D
Secondary branches (L < 20m)
E
RS232-RS4854 Converter
TN
Terminal N
TN+1 Terminal n+1
T1
Terminal 1
T2
Terminal 2
T3
Terminal 3
T4
Terminal 4
LOGICS
COOLING/HEATING SWITCHING
Four logics are present to select the thermostat operating modes according to the
controller configuration setting parameter P00):
-
Local: user choice made through the key
-
Distance: depending on the Digital Input DI1 status (contact
logic: see configuration parameters of board)
-
Depending on water temperature
summer
NB: in case of water sensor alarm, the controller returns to the Local mode temporarily.
-
depending on air temperature
40
winter
Water
tempera-
ture