MYCOMFORT LARGE
> 0: fan off
> 1: extra-low speed
> 2: low speed
> 3: medium speed
> 4: high speed
-
"Air Temperature" register: room temperature read by the controller and shown
on the display (NB: this temperature corresponds to the reading of the remote
probe if the controller is located on the unit, or the reading of the internal probe
in the case of a wall-mounted controller and remote probe disconnected)
GB
-
"Humidity" Register: room humidity read by the controller via the probe associated
with the temperature probe used
-
"Water Temperature" register: value read by the water probe (SW)
-
"P00" Register: "Controller configuration" parameter
-
"T. Active setpoint" Register: setpoint used for temperature control
-
"T. User setpoint" Register: setpoint programmed by the user (it may differ from
the active setpoint due to corrections based on economy logics,...or use of the
setpoint imposed by the supervision software)
-
"LCD version" Register: defines the controller type and software version installed
(0xHHSS: HH: ASCII character, SS:sw version)
-
"P09" Register: "Digital output 1 Configuration" parameter
-
"P10" Register: "Digital output 1 Logic" parameter
-
"P11" Register: "Digital output 2 Configuration" parameter
-
"P12" Register: "Digital output 1 Logic" parameter
-
"P14" Register: "Configuration of analog outputs" parameter
-
"Analog output 1" register: value of analogue output 1 expressed as a % of the
full scale 0-10V
-
"Analog output 2" register: value of analogue output 1 expressed as a % of the
full scale 0-10V
Description of read/write registers [R/W]
-
"Digital 1" Register:
Bit 15
Bit 14
Bit 13
En.Min/M
En.Vel
ax
En.Set
Bit 7
Bit 6
Bit 5
-
-
Lock
> On/Off: On/Off via supervision system
> S/W: selection of operating mode via supervision system (0: Cooling, 1: Heating);
N.B.: if the unit configuration (parameter P00) provides for summer/winter
changeover based on water or air temperature, the resulting mode selection will
override the command from the supervision system (which is thus substantially
ignored))
> RE: selection of Heating element via supervision system
> Eco: Economy mode ON via supervision system
> MinT.: enabling of Minimum Temperature control via supervision system; N.B.:
actual activation remains at the local discretion of each fan-coil unit based on
the air temperature probe reading
> Lock: keypad lock (0: unlocked, 1: locked)
> En.On/Off : enabling of On/Off control via supervision system
> En.S/W: enabling of mode control via supervision system
> En.RE: enabling of selection of heating element function via supervision system
> En.ECO: enabling of economy mode activation via supervision system
> En.MinT: enabling of selection of Minimum Temperature logic via supervision
system
> En.Set: enabling of forced override of setpoint via supervision system
> En.Min/Max: enabling of setpoint thresholds via supervision system
> En.Vel: enabling of selection of fan speed via supervision system
FC66002638 - rev. 05
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
H
Bit 12
Bit 11
Bit 10
Bit 9
En.Min
En.EC
T
O
En.RE En.S/W
L
Bit 4
Bit 3
Bit 2
Bit 1
MinT
Eco
RE
S/W
-
"Scheduling" register: ON/OFF time programming via supervision system
> 0: scheduling disabled
> 1: scheduling enabled for ON/OFF
> 2: scheduling enabled with SETPOINT
-
"Cooling - Setpoint" Register: setpoint imposed by supervision system for the
Cooling mode
-
"Heating - Setpoint" Register: setpoint imposed by supervision system for the
Heating mode
-
"Minimum Setpoint – Cool." Register " : lower limit for setpoint in cooling mode
-
"Maximum Setpoint – Cool." Register " : upper limit for setpoint in cooling mode
-
"Minimum Setpoint – Heat." Register " : lower limit for setpoint in heating mode
-
"Maximum Setpoint – Heat." Register " : upper limit for setpoint in heating mode
-
"Speed" Register: selection of fan speed via supervision system; in the case of
modulating fan control, it expresses the percentage of speed used in the manual
mode
-
"Economy Correction" Register: correction of setpoint in the case of economy
mode imposed by supervisor (this correction is an amount subtracted from or
added to the setpoint, based on the operating mode)
-
"Modulating fan mode" Register: selection of the mode in the case of modulating
fan control: 0 = fan OFF; 1=manually forced fan operation ; 2=automatic fan
operation
SELF-DIAGNOSIS PROCEDURE
This procedure allows you to check whether the individual outputs of the controller
function correctly.
To run the procedure, follow the directions below:
-
switch the thermostat off
Bit 8
En.On/O
ff
-
push the
Bit 0
On/Off
-
use the
the password for self-diagnosis (30) and press
will be displayed:
48
at the same time
level 1: password entry
keys to change the value on the display until arriving at
. The following screen