Installation
Vernatherm Ajustment Instructions
NOTE: The Vernatherm TMA valve is NOT factory preset. Upon installation, the temperature
of this valve must be checked and adjusted to ensure delivery of a safe water temperature.
Water in excess of 110°F (43°C) may cause scalding.
F
CHECK THE TEMPERATURE AND ADJUST IF NECESSARY (THE RANGE OF THE VALVE IS 95°F–115°F (35°C–43°C). TO ADJUST THE
TEMPERATURE, FOLLOW THE PROCEDURE BELOW:
•
LOOSEN TEMPERATURE LOCKING NUT WITH WRENCH.
•
USING A BLADE SCREWDRIVER, TURN THE ADJUSTMENT STEM COUNTERCLOCKWISE TO INCREASE THE TEMPERATURE OR
CLOCKWISE TO DECREASE THE TEMPERATURE (FIGURE 13).
•
ONCE DESIRED TEMPERATURE IS REACHED, TIGHTEN NUT TO PREVENT TEMPERATURE CHANGE.
G
CLEAN SPRAYHEAD IF NECESSARY. SEE PAGE 25 FOR SPRAYHEAD MAINTENANCE AND REPAIR PARTS. ADJUST THE VOLUME
CONTROL VALVE, IF NECESSARY, TO CONTROL THE FLOW OF WATER.
H
ATTACH PEDESTAL ACCESS PANEL WITH HARDWARE PROVIDED.
I
ATTACH KICK PLATE TO PEDESTAL BASE WITH HARDWARE PROVIDED.
Bradley Corporation • 215-1187 Rev. N; EN 06-915B
TEMPERATURE
ADJUSTMENT
STEM
Figure 13
TDB3108, WF3208 Terreon
TEMPERATURE
LOCKING
NUT
4/6/2007
®
54" Circular
19