Assigning Dali Buses To Seetouch Qs Wallstations; Verifying Dali Lights Connected To Dali Bus 1 And Bus 2 - Lutron Electronics Energi Savr Node QS DALI Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 13
Energi Savr Node
Assigning DALI buses to seeTouch
WARNING! Danger of Shock. May result in serious injury or death. DO NOT WIRE WHEN LIVE! Switch off power via circuit
breaker before wiring or servicing the Energi Savr Node QS unit.
Buttons and LEDs on the front of the unit are used for troubleshooting. If wiring is exposed when accessing buttons and
LEDs, the unit must be accessed by a certified electrician, following local codes.
1. Enter QS wallstation into programming mode (press and hold top and bottom buttons on the QS wallstation until its LEDs start
scrolling).
2. Lights on buses previously assigned to this QS wallstation will go to low-end. Unassigned buses will go to high-end.
3. To assign DALI Buses to a QS wallstation:
a. Identifying buses (at the Energi Savr Node QS DALI unit)
i. Single-tap DALI 1 button to select bus 1. Ballast(s) on bus 1 starts flashing. DALI 1 LED starts flashing.
ii. Single-tap DALI 2 button to select bus 2. Ballast(s) on bus 2 starts flashing. DALI 2 LED starts flashing.
iii. If a bus is flashing, single-tapping that bus again will cause it to stop flashing.
b. Assigning buses to the control (at the Energi Savr Node QS DALI unit)
i. After determining which bus (ex: bus 1) you want to assign to the control, press and hold the corresponding bus button (ex: DALI
1 for bus 1) until the LED corresponding to the button (ex: DALI 1 LED) starts to flutter (approximately 3 seconds).
ii. Release the button. The ballast(s) on the assigned bus will go to low-end if successful.
iii. The corresponding LED goes ON if the assignment was successful.
c. Un-assigning buses (at the Energi Savr Node QS DALI unit)
i. If a bus is assigned (ex: bus 1), press and hold the corresponding bus button (ex: DALI 1 for bus 1) until the LED corresponding
to the button (ex: DALI 1 LED) starts to flutter (approximately 3 seconds).
ii. Release the button. The ballast(s) on the assigned bus will go to high-end if successful.
iii. The LED goes OFF if the un-assignment was successful.
4. Exit programming mode from QS wallstation (press and hold top and bottom buttons on the QS wallstation until its LEDs stop
scrolling). All lights should go to their previous levels (levels before entering programming mode).

Verifying DALI lights connected to DALI bus 1 and bus 2:

1. Enter Test mode: - Press and hold Test Button on the Energi Savr Node QS DALI unit until the Test LED starts flashing.
DALI 1 button:
Each button press cycles the lights between:
• Bus 1 going to high-end
• Bus 1 going to low-end
• Bus 1 flash
DALI 2 button:
Each button press cycles the lights between:
• Bus 2 going to high-end
• Bus 2 going to low-end
• Bus 2 flash
2. Exit Test mode: press and hold Test button until Test LED stops flashing.