Product overview
WARNING! Danger of Shock. May result in serious injury or death. DO NOT WIRE WHEN LIVE! Switch off power via circuit
breaker before wiring or servicing the Energi Savr Node QS unit.
Buttons and LEDs on the front of the unit are used for troubleshooting. If wiring is exposed when accessing buttons and
LEDs, the unit must be accessed by a certified electrician, following local codes.
The DALI Energi Savr Node QS unit powers two DALI buses and supports communication for a maximum of 64 DALI ballasts or
other controllable illumination drivers per link, 128 total. An Energi Savr Node QS system consists of an Energi Savr Node QS units,
ballasts, inputs, wallstations, and QS devices. The diagram on the previous page shows a typical system topology.
• All ballasts and Energi Savr Node QS units are powered by mains voltage (Live and Neutral).
• Two additional wires for digital communication per DALI bus (DA1/DA1 DA2/DA2).
• The DALI bus may be treated as mains voltage and thus may be run within the same conduit.
• The DALI bus wires are non-polarised and can be run as a daisy chain, T-tap, star, or in any combination.
• Only one Energi Savr Node QS DALI unit or DALI Bus Supply may be connected per DALI bus.
• The Energi Savr Node QS DALI unit has inputs for:
– 128 total ballasts. (64 per DALI bus)
– 4 daylight sensors (model: EC-DIR-WH)
– 4 occupancy sensors (models: Lutron LOS series)
– 4 IR receivers (models: EC-DIR-WH, EC-IR-WH)
• The QS Link can have up to 100 zones and 100 devices.
• The Energi Savr Node QS unit occupies 1 device position and up to 32 zone positions.
• In a system with multiple Energi Savr Node QS units, a maximum of 100 daylight sensors and 100 occupancy sensors are permitted.
Refer to the following step-by-step guide for proper Energi Savr Node QS unit installation.
– To connect multiple Energi Savr Node QS units into a single system, use the QS link (pin 1,3, and 4 only). See PELV Wiring
Example on page 8 for more details.
Wiring overview
PELV
Inputs
1
1
2
2
3
3
4
4
Energi Savr Node
Hi Temp
QSNE-2DAL-D
Test
230 V~ 50/60 Hz 100 mA
www.lutron.com
Power
+44.(0)20.7680.4481
L
N
0,5 N m
8 mm
Mains
Wiring
Lutron
2
|
®
QS DALI
TM
Ethernet
DALI 1
QS
Programming
DA1/DA1
Link
Jack
QS
Ethernet
DALI 1 DALI 2
QS
TM
Z096
N1771
|
Installation Guide
DALI 2
DA2/DA2
®
V
D E
Energi Savr Node
QS DALI Installation Guide