Energi Savr Node
Step 2: Mains voltage wiring
The Energi Savr Node QS unit operates at 220-240 V . Use the
following instructions to wire line voltage to the Energi Savr Node
QS unit.
WARNING! Danger of Shock. May result in serious
injury or death. DO NOT WIRE WHEN LIVE! Switch off
power via circuit breaker before wiring or servicing the
Energi Savr Node QS unit.
Buttons and LEDs on the front of the unit are used for
troubleshooting. If wiring is exposed when accessing
buttons and LEDs, the unit must be accessed by a certified
electrician, following local codes.
1. Turn power off.
2. Use 1,0 mm
to 4,0 mm
conductors (depending on breaker
2
2
rating) to feed the mains wiring. The device draws less than
100 mA.
3. Strip 8 mm of insulation off the mains cables.
4. Wire the mains to the terminals labelled L, N, and .
A three-position terminal block is provided. Do not wire L or N
wires to the
terminal.
5. The recommended installation torque is 0,5 N·m
6. The Energi Savr Node QS unit is earthed through the
Attach the earth wire.
7. Close front cover of panel.
8. Turn on the circuit breaker to power up the Energi Savr Node
QS unit. The POWER indicator on the Energi Savr Node QS unit
will display a green light continuously when properly powered
up. If the indicator does not light, turn off power, then check the
mains voltage wiring and repeat this step.
9. Turn power off.
Note: If additional wiring space is required, the Energi Savr Node
QS unit can be removed from the DIN rail while wiring. Follow
the instructions in Step 1: Mounting the Energi Savr Node QS
unit on page 3.
Lutron
4
|
®
|
QS DALI
Installation Guide
TM
terminal.
1
1
3
3
1
1
2
2
QS
3
3
4
4
Energi Savr Node
Hi Temp
QSNE-2DAL-D
Test
Hi Temp
230 V~ 50/60 Hz 100 mA
www.lutron.com
Power
+44.(0)20.7680.4481
L
N
0,5 N m
8 mm
Test
Power
L
N
0,5 N m
L N
Energi Savr Node
QS DALI Installation Guide
TM
2
2
4
4
Ethernet
DALI 1 DALI 2
QS
TM
®
Z096
Energi S
N1771
QSNE-2DAL-
230 V~ 50/60 H
www.lutron.com
+44.(0)20.7680.4
V
D E
8 mm
Mains Wiring:
• 1,0 mm
to 4,0 mm
2
2
• Strip length: 8,0 mm
• Torque: 0,5 N
m
•
QS