English
Español
Energi Savr Node
Using LEDs to troubleshoot
WARNING! Danger of Shock. May result in serious injury or death. DO NOT WIRE WHEN LIVE! Switch off power via circuit
breaker before wiring or servicing the Energi Savr Node QS unit.
Buttons and LEDs on the front of the unit are used for troubleshooting. If wiring is exposed when accessing buttons and
LEDs, the unit must be accessed by a certified electrician, following local codes.
LED
Normal operation
Power
Green: Continuous On
DALI1, DALI 2
Green: 1 flash per second
(DALI Bus Status)
IR (Infrared Receiver
Photo (Daylight
Sensor
Green: 1 flash per second
Occ (Occupancy
Sensor)
QS (QS Link Status) Green: 1 flash per second
Green: Flashing
Ethernet
Yellow: Continuous On
Off
Test
Hi Temp
Off
(Temperature Status)
Energi Savr Node
QS DALI Installation Guide
TM
English
Français
Português
|
QS DALI
Installation Guide
TM
Problem indicator
Green: 5 flashes per second
Red: 5 flashes per second
Red: Continuous on
Red/Green: alternating 1 flash
per second
Red: 1 flash per second
Red: 1 flash per 7 seconds
Green: 1 flash per 7 seconds
Green: 5 flashes per second
Off
Green: 1 flash per 7 seconds
Green: 5 flashes per second
Off
Off
Off
Red: 5 flashes per second
Red: 5 flashes per second
Red: continuous On
Italiano
Deutsch
Probable cause
General system failure
Miswire or DALI bus error
DALI bus externally shorted
Bus slowed because of over-
temperature
Link stopped because of over-
temperature
More than one supply
powering link
Input disconnected,
communication lost
Incorrect data
No connection ever made
Link disconnected,
communication lost
Incorrect data
No connection ever made
Ethernet not connected
Ethernet not connected
Test failed- see DALI LEDs
Over-temperature
Over-temperature, unit
disabled
中文
Lutron
11
|
®