Energi Savr Node
Step 4: Input group wiring
To connect a daylight sensor, occupancy sensor and/or infrared
receiver, refer to the instruction sheets provided with the
devices. Diagrams for the PELV input terminals are shown
below.
WARNING! Danger of Shock. May result in serious
injury or death. DO NOT WIRE WHEN LIVE! Switch off
power via circuit breaker before wiring or servicing the
Energi Savr Node QS unit.
Buttons and LEDs on the front of the unit are used for
troubleshooting. If wiring is exposed when accessing
buttons and LEDs, the unit must be accessed by a certified
electrician, following local codes.
* Note: Only one IR device may be connected per input. If the IR
signal from a daylight sensor is connected, a wall control may not
be connected to the same input, and vice-versa.
** Connect the gray wire instead of the blue wire on LOS Series
occupancy sensors that include -R in the model number.
Sample applications: preconfigured modes require no commissioning
Bus 1
Daylight
Occupancy
Sensor
Sensor
Perimeter
Interior
Preconfigured mode 1
Perimeter daylighting
* Four fixtures shown on bus 1 and eight fixtures shown on bus
2, however, up to 64 ballasts can be connected per bus.
Default Behaviour for Input Connections
Connected to input group 1
Connected to input group 2
Connected to input group 3
Connected to input group 4
Lutron
6
|
®
QS DALI
TM
Bus 2
Energi Savr
Node QS
unit
Wired to
input
group 3
Occupancy sensor
Daylight sensor
Controls bus 1 only
Controls bus 1 only
Controls bus 2 only
Controls bus 2 only
Controls both buses
Controls both buses with equal daylight gain
Controls both buses
Controls both buses with lower daylight gain on bus 2
|
Installation Guide
20 V – 20 V
IR – IR Receiver*
Photo – Daylight Sensor
Occ – Occupancy Sensor
Com – Common
1
1
2
2
3
3
4
1
4
3
Hi Temp
Test
Power
L
N
Energi Savr Node
Hi Temp
QSNE-2DAL-D
Test
230 V~ 50/60 Hz 100 mA
www.lutron.com
Power
+44.(0)20.7680.4481
L
N
0,5 N m
8 mm
Bus 1
Occupancy
Sensor
Occupancy
Sensor
Perimeter
Preconfigured mode 2
Two zones with occupancy sensors
* Six fixtures shown on each bus. However, up to 64 ballasts
can be connected per bus.
Daylight
Occupancy
Sensor*
Sensor
IR Transmitter
Group 1 shown
Group 2 shown
1
QS
Ethernet
• 0,5 mm
1
2
2
3
QS
Ethernet
DALI 1 DALI 2
3
4
4
• Strip length: 6,0 mm
Energi Savr Node
QS
TM
®
QSNE-2DAL-D
Z096
N1771
230 V~ 50/60 Hz 100 mA
www.lutron.com
+44.(0)20.7680.4481
• Torque: 0,5 N
0,5 N m
8 mm
QS
Hi Temp
TM
D E
V
NOTE: There are four
Input Group 1
Power
input groups. Each
L
N
group is wired in the
same way and is
shown above.
Input Group 3
1
3
Hi Temp
Power
L
Wired to
Energi Savr
input
Node QS
group 1
unit
Bus 2
Wired to
input
group 2
Interior
Energi Savr Node
QS DALI Installation Guide
TM
IR
Receiver*
IR Transmitter

Input Group Wiring:

1
2
2
DALI 1 DALI 2
to 4,0 mm
2
2
3
4
4
m
Energi Sa
Z096
QSNE-2DAL-D
N1771
Test
230 V~ 50/60 H
www.lutron.com
Input Group 2
+44.(0)20.7680.44
0,5 N m
8 mm
Input Group 4
1
2
2
QS
3
4
4
Energi Savr Node
TM
QSNE-2DAL-D
Test
230 V~ 50/60 Hz 100 mA
www.lutron.com
+44.(0)20.7680.4481
N
0,5 N m
8 mm
QS
®
Et
Q