The burner does not start:
The transformer does not works during pre-washing, and then the burner stops: - Transformer failure
The burner does not start: (pre-heated version)
The burner starts but then stops due to missed ignition:
The burner ignites but then shuts down:
The fuel atomization is bad
The combustion is abnormal (smoking flame, sooting) :
The fuel drips through the nozzle after burner shutdown:
No production of hot sanitary water:
Very little production of hot sanitary water:
Little production of hot water for heating:
B
TROUBLESHOOTING
pag.18
Compact ABCD
- On-Off switch open
- Safety fuse blown out
- Boiler thermostats open
- Control box in shutdown mode
- Condenser failure
- Burner's motor failure
- Control box failure
- Ignition cables failure
- Electrodes grounded
- On-Off switch open
- Safety fuse blown out
- Boiler thermostats open
- Control box in shutdown mode
- Condenser failure
- Burner's motor failure
- Pre-heater thermostat failure
- Pre-heater resistance failure
- Missed ignition in absence of spark:
- Missed ignition in presence of spark:
- Electrodes dirty
- Electrodes failure
- Electrodes gap wrong
- Ignition cables failure
- Ignition transformer failure
- Control box failure
- Lack of fuel into the tank
- Valve closed on suction pipe
- Filters clogged
- Nozzle clogged or worn out
- Fuel feeding pressure too low
- Burner pump failure
- Solenoid valve failure
- Excess of combustion air related to nozzle output
- Control box failure
- Nozzle worn
- The photocell does not detect the flame after burner
ignition
- Photocell failure
- Excess of combustion air related to nozzle output
- Wrong adjustment of firing head
- Check nozzle
- Check filters
- Check pump pressure
- Check combustion air flow rate
- Check fan turbine
- Check the adjustment of:
- air damper
- firing head
- Verify that the room has enough ventilation
- Check the solenoid valve sealing and, if necessary,
carefully clean it.
- Pump failure
- Boiler temperature too low
- Differential pressure switch failure or with open
contacts
- The 3-way valve is jammed
- Boiler temperature is too low
- Calcareous deposits on the heat exchanger
- The 3-way valve is in normal position
- Pump speed too low
- Pump speed too low
- Room temperature thermostat failure