The EXP series controllers require 24 VDC nominal input power. Power is provided to the controller
using terminal blocks J1 through J4. Large, redundant input power terminal blocks are provided to help
support large cables designed to minimize voltage drop in the line. Connect positive power leads to J1
and J2 and negative power leads to J3 and J4. Each terminal block is capable of accepting a 24 AWG
to 6 AWG conductor. Conductor sizes and cable length must be designed for the specific application
and should be fused according to the table below.
Nominal
Input Voltage
24 VDC
Battery / Power
Source
24 V

Motor Power Wiring

Power is provided to the R, S, and T actuator phases using terminal blocks J6 – J8. The J9 terminal
block provides an internal connection to the controller case for PE ground connection to the Motor. The
terminal blocks are capable of accepting 24 AWG to 6 AWG (0.2 – 16 mm
2
12 AWG (2.5 mm
) wire is required for rated output power.
The controller is capable of providing three phase current of up to 30 A peak for one minute and 25 A
continuously. Conductor sizes and cable length must be designed for the specific application. The
maximum motor cable length is 20 feet (6 meters). For best ECM practices use shielded cable with the
shield connected in the cable gland.
EXP 24 Controller R
Function
Motor R Phase
Motor S Phase
Motor T Phase
Motor PE
EXP 24 Manual
PN 47676
Revision H
Input Voltage
Peak Input
Range
Current, DC
18 – 32 VDC
+
30 Amp
_
_
Input Power Wiring
20 ft. max
S
T
PE
Shield
48
Maximum
Continuous Input
Current, DC
30A
25A
-
EXP24 Controller
+
R
S
T
PE
Terminal
J6
J7
J8
J9
Fuse
30 Amp Very Fast
Blow
2
) conductors. A minimum of
Actuator / Motor
1/9/14
Exlar Corporation
952-500-6200