Start up
- Setting data table - Air regulation
The burner leaves the factory with the following calibration values:
BURNER
CODE
3147867
CONFORT 100
3147824
SP 110
3147861
SP 235
The settings above are basic settings. In case of operation at 60 Hz, the burner must be recalibrated by closing the air shutter so as to
reduce the amount of incoming air.
1
B
A
A
!
Risk of air blast!
Continuously check CO, CO 2 and soot emissions when adjusting the output of
the burner. Optimise combustion values in the event of CO formation. CO must
not exceed 50 ppm.
14
www.ecoflam-burners.com
NOZZLE
gph
Type
spry
1,5 DELAVAN 60°W
1,75 DELAVAN 60°W
3,5 DELAVAN 60°W
2
PUMP
BURNER
PRESSURE
OUTPUT
bar
kg/h
11 - 13
6,32
11 - 14
7,53
10 - 15,5
15,5
FIRING HEAD 
AIR DAMPER
SETTING
SETTING
Pos.A
39,5
1,9
39,5
2,2
29,5
2
Low Flame air adjustment (1)
Intervene on screw A in the picture:
• turning it anti-clockwise increases the
flow rate;
• turning it clockwise decreases the
flow rate.
High Flame air adjustment (1)
Intervene on screw B in the picture:
• turning it anti-clockwise increases the
flow rate;
• turning it anti-clockwise decreases the
flow rate.
Firing head setting (2).
Intervene on the screw shown in the
picture:
• turn it using a hex spanner until it
reaches the desired value (index from 0 to
5).