Rectifying malfunctions

Malfunction
LED
flashes every
2 seconds, no
flush actuation.
No LED is lit.
Water is
flowing from
the overflow.
18014401053566091-1 © 07-2018
967.986.00.0 (01)
Cause
Battery almost
1)
dead
Control unit is in
standby mode
Battery dead
Trap or discharge
pipe clogged
Discharge pipe
doubly trapped
Insufficient
ventilation pipe in
the drainage
system
Rectification
Replace the battery. →
See "Replacing the
battery", page 46.
Press the <TEST>
button. Control unit
shows the current
operation mode.
Press the <TEST>
button. Replace the
battery if nothing appears
on the display. → See
operation manual
967.986.00.0.
Close the water tap.
Contact a skilled person.
Close the water tap.
Contact a skilled person.
Close the water tap.
Contact a skilled person.