Siemens SIVACON S8 Manual Del Usuario página 34

Ocultar thumbs Ver también para SIVACON S8:
Tabla de contenido

Publicidad

SIVACON
Maintenance Check List
Inspection and service of cubicles with a withdrawable design
For the withdrawable design the following maintenance work must be performed in addition to general maintenance of low-voltage switchboards.
For the installed equipment, the manufacturer's operating instructions take precedence and must be complied with.
Item
Work to be performed
Notes / Criteria
No.
4
Visual inspection of
withdrawable units
For the visual inspection the withdrawable unit must be taken out of the cubicle.
4.1
Withdrawable unit
Damage, deformation of the contacts
contacts
Local discoloration due to overheating
Condition of the plastic parts in the area of the contacts
Condition of the grease
Signs of flashovers or creepage tracks
Contact erosion
Signs of loading with sulfurous gases (severe discoloration, formation of pollution layer)
4.2
Withdrawable units
Smooth moving of the contacts in all withdrawable unit positions
mechanism
Opening and closing of the circuit breaker with door-coupling rotary mechanism
5
Visual inspection of
withdrawable unit
compartment
Warning!
The vertical busbar and outgoing busbar in the withdrawable unit may be energized..
5.1
Shutters and cover of the
Mechanical function of the shutter
vertical busbar (if
Covers are completely available
installed)
Contact protection is guaranteed for removed withdrawable unit.
5.2
Soiling, foreign bodies
Dust deposit and pollution
Foreign material within the withdrawable units
6
Servicing withdrawable
units
For the maintenance the withdrawable unit must be taken out of the cubicle.
6.1
Clean withdrawable unit
See operating instructions for each supplied type: 8PQ9800-3AA48, 8PQ9800-7AA80 or
contacts
8PQ9800- 6AA81
6.2
Grease withdrawable unit
See operating instructions for each supplied type: 8PQ9800-3AA48, 8PQ9800-7AA80 or
contacts
8PQ9800- 6AA81
7
Servicing withdrawable
unit compartment
Warning! Switch off and lock out all power supplying the affected part of the low-voltage switchboard before commencing
servicing work
7.1
Contact points at vertical
Local discoloration due to overheating
and outgoing busbar
Condition of the plastic parts
Signs of flashovers or creepage tracks
Contact erosion
Pollution and foreign bodies
Signs of loading with sulfurous gases (severe discoloration, formation of pollution layer)
8PQ9800-7AA73
Yes
No
Remarks / Result
B3

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido