Ingeteam
0020H
Insulation fault in DC circuit.
There are three possible causes:
•
There is an insulation fault on the battery earthing circuit.
•
The fault current or differential current protection has tripped.
0400H
Manual shutdown. Check that the inverter has not been shut down manually from the display.
10000H
Inverter overload. The inverter is supplying more power than its maximum power. If the OVERlOAD
operation is activated check the parameters configured.
20000H
AC short-circuit. The most probable cause is a short-circuit in the installation. Check the installation.
5.1.3. Red LED
This is the continuously lit LED indicating that the inverter is manually stopped.
To start it up, this must be done manually, as the Start or Stop status does not change even when the unit loses
power.
In the main menu, highlight the START/STOP option and press
to toggle the status.
The following message is shown on the screen: