HC997-999 – MOD. D
Digital multifunction solenoid metering pump
– P
4.4 P
ROGRAMMING MENU
4.4.1
Proportional functioning by external pulses
4.4.2
Proportional functioning by external pulses 1xN
In this functioning mode there are two parameters to set:
Every time the pump receives a pulse from the water meter it perform the desired
strokes at the programmed frequency.
Example 1xN = 1x15
The pumps gives 15 strokes at 60SPM frequency every time it receives a pulse from the
water meter.
Press the
Press the
ADSP9000033
All manuals and user guides at all-guides.com
PROPORTIONAL FUNCTIONING BY EXTERNAL PULSES
ROPORTIONAL FUNCTIONING
Press the
Press the
Number of strokes to perform.
Setting from 0 to 250.
Frequency of the strokes per minute (Str/m).
Setting from 1 to 150 or 180 (depends on the model).
Str/m = 60
keys to set the desired values.
key to go at the previous menu.
03/09/2015 Rev.1.2
Press the
keys to scroll the menu
entries.
Press the
key to select the desired entry.
keys to scroll the menu entries.
key to select the desired entry.