HC997-999 – MOD. D
Digital multifunction solenoid metering pump
4.4.7 Functioning proportional chlorine Jumo (A – J probe).
The pump doses proportionally by chlorine A – J probe reading
In this functioning, the parameters to set are the following:
ADSP9000033
All manuals and user guides at all-guides.com
A – J ppm
Indicates the range of work Cl –J probe
Setting from 0 to 100.000 ppm.
Set point A - J
Indicates the Cl value to maintain constant.
Setting from 0,01 to 5,00 ppm at step of 0,01.
Prop. L1
Indicates the Cl value that together with the Setpoint value make the
proportional dosing band.
Setting from 0,01 to 5.00 ppm at step of 0,01.(See par. 4.4.8).
% SPM Set
Indicates the dosing frequency of the pump at the Setpoint value.
Setting from 0 to 100%.
% SPM
L1
Indicates the dosing frequency of the pump at the Setpoint value.
Setting from 0 to 100% (See par. 4.4.8).
Press the
keys to adjust the measured value.
Calibration Gain
The Probe A-J don't require zero calibration, wait until the measure stabilized
maintain the speed flow between 30 and 90 l / min. and measure the ppm
whit DPD clorine free test Kit
Make corrections using the buttons
Restore Par.
Restoring the default parameters of the chlorine functioning.
Press the
key to go back at the previous menu.
03/09/2015 Rev.1.2
PROPORTIONAL FUNCTIONING BY CL SIGNAL
.
ENGLISH
38/100