Ingeteam
Select the connection type: Ethernet.
IP: IP address acquired by the inverter
Port: 502
Modbus node: 01
Alias: ISS 1Play
Phase: R
SOC maximum: This value is informative. Not used for the monitoring strategy.
Set the same value as the INGECON SUN STORAGE 1Play as SOC MAX.
SOC minimum: Not used for the monitoring strategy. Set the same value as the
INGECON SUN STORAGE 1Play as SOC MIN.
Click on Find . If the unit is correctly connected and configured a warning is
displayed with the device's serial number and firmware.
Finally, save the settings by clicking on Save .
5. Configure the GRID reading.
Click on the Grid icon and configure the Power Meter Id parameter with the name
provided to the previously configured ISS 1Play.
All manuals and user guides at all-guides.com
Installation and configuration of a UPS (Back-up) system
23