8.2.- Audible alarms.
• Discharge. Beeps every 4 sec. wiht Led (c) active, to inform loads are supplied from the battery. The alarm stops
upon restoration of the mains supply. If you want to silence the alarm see paragraph 8.3.
• Low battery. Beeps each 0.5 sec. wiht Led (c) active, it indicates the end of autonomy. Shortly the UPS will block
to protect the battery and when the mains returns, the unit will start automatically.
• Overload. Modulated every 0.5 seconds with active LED (f), moderate overload.
Permanent alarm with active LED (f), high overload.
• Replace battery. Continuous alarm wiht the Led (g) lit. Perform self-test as per paragraph 7.4.
8.3.- Alarm silence.
• On the "Autonomy" mode the led (c) lit and (a) turned off an audible modulated, alarm is activated. Press the "ON"
key (6) for 1 second, the "Discharge" alarm will be inhibited. It is not possible to silence any of the other alarms.
9.- FAULT LOCALISATION.
• See table 1.
10.- TECHNICAL CHARACTERISTICS.
Input.
Input voltage AC: ................................................................. 100 V (76-130 V); 110 V (80-138 V); 115 V (83,5-140 V);
Input frequency: .................................................................. 50 Hz or 60 Hz ±5 Hz (auto detection).
Output.
Power depending on model: ............................................... See table 2.
Output voltage on inverter: ................................................. 100 V, 110 V, 115 V, 120 V, 208 V, 220 V, 230 V, 240 V.
Output voltage precision on inverter: ................................. ±2 %, excepting in UPS-3000 NX / NX R to 110 V ±3 %.
Inverter working: .................................................................. PWM (Sine-wave).
Output frequency: ............................................................... 50 Hz or 60 Hz.
Output frequency stability on inverter: ............................... ±0.5 %.
Transfer time: ...................................................................... 0 ms.
Overload detection: ............................................................. 105 % for 10 seconds or 130 % ±10 % for 300 ms..
Harmonic distortion: ............................................................ < 3 % of T.H.D. at linear load.
Efficiency: ............................................................................ > 85 %.
120 V (87-140 V); 208 V (152-260 V); 220 V (160-276 V);
230 V (167-280 V); 240 V (174-280 V).