Technical Data; Electrical Data - Riello RL 25/1 BLU Instrucciones De Instalación, Funcionamiento Y Mantenimiento

Quemadores de gasóleo
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4.3

Technical data

Model
Power
(1)
Delivery
(1)
Fuel
Max. viscosity at 20 °C:
Net Calorific Value
Density
Intermittent
Pump
Output at 12 bar
Pressure range
Fuel temperature
Nozzles
Standard applications
Room temperature
Combustion air temperature
Noise levels
Sound pressure
(3)
Sound power
Weight (including packaging)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1,013 mbar - Altitude 0 m a.s.l.
(1)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output. The sound power
(2)
is measured with the "Free Field" method, as per EN 15036, and according to an accurate "Accuracy: Category 3" measurement, as described in
EN ISO 3746.
4.4

Electrical data

Model
Electrical power
Motor
Fan motor capacitor
Ignition transformer
Single-phase max. absorbed electric
power main electrical supply
Protection level
20156111
Technical description of the burner
min - max
kW
Mcal/h
kg/h
kWh/kg
Mcal/kg
kg/dm3
kg/h
bar
°c max
number
°C
°C max
dB (A)
kg
1 Ph
rpm
V
W
A
µF
V1 - V2
I1 - I2
W max
Light oil
2
6 mm
/s (1.5°E - 6 cSt)
Intermittent (min. 1 stop in 24 hours)
One-stage (all - nothing)
Boilers: water, steam, diathermic oil
220-240V - 2x12kV
8
GB
RL 25/1 BLU
115 - 260
99 - 224.4
10 - 22
11,8
10.2 (10,200 kcal/kg)
0.82 - 0.85
45
8 - 25
60
1
0 - 40
60
71
82
43
RL 25/1
1 N ~ 230 50 Hz
2800
230
300
2.4
12.5/450
0.2A - 30mA
550
IP 54
Tab. A
Tab. B

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

2015602420157095

Tabla de contenido