21 INDICATION WITHOUT
CONNECTION OF THE ACTIVATION
OF A SOLENOID VALVE
1.
There must be no lead connected to the instrument;
2.
Place the instrument as close as possible to the solenoid
valve;
3.
Press the ON button. The green indicator indicates that the
instrument is in operation;
4.
The clockwise or anticlockwise rotation indicator lights,
indicating the presence of the field generated during the
activation.

22 TECHNICAL SPECIFICATIONS

22.1 ELECTRICAL CHARACTERISTICS

Maximum rated voltage:
600V, CAT III
Operating voltage, in phases rotation use:
With connections:
40 to 600VAC between phases (see
§ 5.1 and 7)
Without connection:
120 to 400V
§ 6)
Frequency of operation:
15 to 400Hz
Test current (per phase):
less than 3.5mA
Power supply:
9V battery (6LR61, 6LF222, 1604A,
NEDA 1604)
Consumption less than 20mA.
L1, L2, L3 lights are on , since 100V voltage between phases and
neutral.
English
between phases (see
AC
23