Digital display 
 
In monitoring or parameter setting mode, the green digit on the left displays the rank of the parameter while the 
other digits (red) indicate the value of the parameter. 
 
Note:  When  the  CYCLIC  2020  is  powered  on,  the  display  indicates  "_  _  _  _"  during  initialization  (~1s),  then  the 
EPROM version "2.04" during ~3 seconds. 
2.4.1.
Management of COMPRESSED AIR by CYCLIC 2020 
Two cases can arise: 
1) If the hygrometry sensor is managed, the display indicates periodically the regulation pressure measured by the 
system  for  1  minute  and  the  hygrometry  temperature  for  5  seconds.  When  the  hygrometry  temperature  is 
displayed,  the  green  digit  indicates  the  air  treatment  unit  in  service  ("A"  or  "b")  in  the  case  of  independent 
hygrometry management. 
2) If the hygrometry sensor is not managed, the display indicates the regulation pressure constantly. 
 
If FLEXO mode is selected, the green digit indicates "F"; otherwise it remains blank. 
2.4.2.
Management of VACUUM by CYCLIC 2020 
In normal mode the display only indicates the regulation pressure. 
If FLEXO mode is selected, the green digit indicates "F"; otherwise it remains blank. 
 
If a pump didn't run during the last 24 hours, then it is switched on during a forced running of 15 minutes. 
This function will avoid the seizing of the pump. 
This 15 minutes time is modifiable by the paramater H from 0 to 30 minutes. 
If H = 0 min, this function is inactive 
2.4.3.
Hour meters 
If the value is less than 9999h, the display indicates this value on the four red display windows and upwards of 
10000h, the four red display windows indicate "10.00" without the units figure. 
519112‐02 
CYCLIC 2020 
2.5.
Keys 
"Increase" [+] and "Decrease" [‐] keys: 
increase or decrease the value of a setting parameter. 
Keys only activated in parameter setting mode. 
 
 
"high pressure threshold" and "low pressure threshold" keys, 
Scrolling up or down: 
scrolls through the list of settings in monitoring and parameter setting modes. 
 
 
"Stop buzzer" key: 
 
deactivates the buzzer for 15 minutes. Self‐activating. 
The buzzer sounds (for 2 seconds) when a new alarm occurs. 
No effect on alarm synthesis relay. 
 
"test LEDs" key: 
Pressing  this  key  lights  up  all  the  LEDs,  indicators,  display  digits  and  activates  the 
buzzer for test purposes.  
 
"Network pressure" key: 
Pressing this key causes alternating display of network pressure (with green digit ""), 
cylinder A pressure (with green digit "A") and cylinder B pressure (with green digit "b") 
if  they  are  managed  (with  air  only)  [SW1‐7  (network  pressure)  and  SW2‐3  (cylinder 
pressure/ analogue or logical)]. 
If the network is not managed, the digital display indicates "_ _ _ _ " 
 
"Hygrometry / Temperature" key: 
‐ with air:  Pressing this key causes alternating display of the hygrometry temperature 
if it is managed (SW1‐6) with the green digit indicating "H" for management per 
hygrometry line or "A" or "b" (air treatment unit in service) for independent 
hygrometry management. If it is not managed, only the room temperature is displayed 
with the green digit indicating "t".  
‐  with  vacuum:  The  temperature  probe  measurement  with  the  green  digit  indicating 
"t". 
 
The LED comes on steady if faults have been stored. When this key is held depressed, 
all  the  faults  that  have  occurred  since  powering  on  (or  the  last  fault  clearing)  are 
displayed. If the LED is off, no faults are stored. 
 