2.8.
Inputs 
2.8.1.
On/Off inputs 
‐ 3 On/Off inputs: 
motor safety [dry contact ‐ NC] 
‐ 1 On/Off input: 
selection of FLEXO mode: open = FLEXO managed  and  closed = FLEXO not managed 
‐ 1 On/Off input: 
switching of air treatment units [NC pulse contact] 
 
 
(only in compressed air mode with independent hygrometry management) 
2.8.2.
Analogue inputs 
In the case of an analogue reading, if the sensor is disconnected or faulty, the display becomes "CC". 
 
‐ 1 control pressure input 
 
Absolute vacuum: 
 
Relative vacuum: 
 
Air: 
 
‐ 1 network alarm pressure input 
 
Absolute vacuum: 
 
Relative vacuum: 
 
Air: 
 
‐ 1 hygrometry input (compressed air only) 
 
Display of "H  LL" (or "A  LL or "b  LL")  if  <  2.7 mA  (connection broken) 
 
2.8.3.
On/Off and analogue inputs (compressed air management only) 
‐ 2 air cylinders frame pressure inputs: 
 
The choice between an analogue and logical reading is made using switch SW2‐3. 
 
Analogue sensor: 
4 mA = 0 bar and 20 mA = 200 bar or 250 bar according to the switch SW1‐1. 
 
Mechanical pressure switch:  contact closed = air cylinders frame pressure OK. 
 
contact open = problem with air cylinders frame pressure. 
 
The number of cylinders sensor managed is indicated by the "P" parameter: 
0 = air cylinder backups not managed 
1 = air cylinder backups on C4A 
2 = air cylinder backups on C4A and C5A 
 
In the case of an analogue reading, if the sensor is disconnected or faulty, the display becomes "CC". 
 
Note: if the air cylinder frames input is a logical input  (pressure switches), when the 
frame A then frame B, the display is "yes" if the contact is closed and "no" if it is open. 
519112‐02 
CYCLIC 2020 
4 mA = 0 mbar and 20 mA = 1100 mbar. 
4 mA = 0 mbar and 20 mA = ‐1000 mbar. 
4 mA = 0 bar and 20 mA = 16 bar. 
4 mA = 0 mbar and 20 mA = 1100 mbar. 
4 mA = 0 mbar and 20 mA = ‐1000 mbar. 
4 mA = 0 bar and 20 mA = 16 bar. 
4 mA = ‐80°C and 20 mA = +20°C 
  key is pressed for 
2.8.4.
PT100 input 
The sensor is used to measure the room temperature in the ‐20°C to +60°C range. 
If  the  sensor  is  disconnected,  the  display  indicates  "tt",  high  temperature  alarm  is  activated  and  the  fan  is 
operating. 
2.9.
Outputs 
‐ 3 on/off outputs: 
order of command A, B or C :  . .......  d ry contact ‐ NO ‐ 250V ‐ 5A (non‐reactive load) 
 
‐ 1 on/off output: 
alarm synthesis: .....................  d ry contact ‐ Reversing switch ‐ 250V ‐ 5A (non‐reactive load) 
As long as an alarm is indicated (steady or flashing red light), the "alarm synthesis" output relay is active. 
As it is if the CYCLIC 2020 is switched off. 
 
‐ 1 on/off output: 
network sensor contact (FLEXO):  NO ‐ 250V ‐ 5A (non‐reactive load) 
It closes when the network pressure reaches the high alarm pressure threshold. 
It opens when the network pressure reaches: the network alarm threshold ‐ hysteresis  
(50 mbar for vacuum; 0.5 bar for compressed air). 
 
Example: 
with vacuum: 
 
if A = ‐880 mbar, 
 
B = ‐830 mbar. 
 
with air: 
 
if A = 12.5 bar, 
 
B = 12 bar 
 
Vacuum pump depressurizations function (with 2 network pressure sensors): 
When a motor stops, the network alarm high threshold exit is closed during 3 seconds (and actuates the opening of 
the atmospheric pressure solenoid valve). 
 
‐ 1 on/off output: 
fan: 
 
‐ 1 on/off output: 
channel in service/backup 
(only for independent hygrometry management) 
The  contact  switches  if  a  hygrometry  fault  occurs  or  a  switching  request  is  made  via  the  "Air  treatment  unit 
switching" on/off input. 
 
‐ 1 on/off output: 
control sensor contact (FLEXO):   NO ‐ 250V ‐ 5A (non‐reactive load) 
 
It is not activated until 6 seconds after powering on. 
 
It closes when the control pressure reaches the high threshold. 
 
It opens when the control pressure reaches the high threshold ‐ hysteresis 
 
(50 mbar for vacuum; 0.5 bar for compressed air). 
 
Example: 
with vacuum: 
 
if A = ‐850 mbar, 
 
B = ‐800 mbar. 
 
with air: 
 
if A = 11.5 bar, B = 11 bar 
 
dry contact ‐ NO ‐ 250V ‐ 5A (non‐reactive load) 
NO ‐ 250V ‐ 5A (non‐reactive load) 
15 