BTL7-A/E501-M _ _ _ _ -A/B/CD/Y/Z(8)-NEX-S32/KA _ _
Micropulse Transducer - Rod Style
9
Adjust with the calibration device (continued)
Set end point
► Bring magnet to the new end point.
► Hold down
for at least 2 s.
⇒ The new end point is set with the last valid end
value.
Adjust end value
► The end value can be changed using
The gradient of the curve changes (See page 19).
► End calibration procedure: Briefly press
simultaneously (< 1 s).
⇒ Set position value is saved.
End adjustment
► Briefly press
and
⇒ The current position value is displayed once the
buttons are released.
Any of the individual steps for settings can be
selected. The adjustment process can be
ended at any time.
1) Briefly press button: Current value is increased or
decreased by approx. 1 mV or 1 µA.
If a button is held down longer than 1 s, the step
interval is increased.
22
english
and
1)
.
and
simultaneously (< 1 s).
LED legend:
LED display
LED1 LED2 At 0...10 V
2
> 2 s
1
1
2
2
1
< 1 s
2
1
2
< 1 s
LED not on
LED green
LED 1 and LED 2 flashing red-green in alternation
LED 1 and LED 2 flashing red-red in alternation
Ignition protection
"nA" and "tb"
Displayed values (example)
At 4...20 mA
9.89 V
19.13 mA
10.00 V
20.00 mA
10.00 V
20.00 mA
8.00 V
16.80 mA
8.00 V
16.80 mA