Idiomas disponibles

5. Connect the utility service to the transfer switch's Service
Disconnect Circuit Breaker terminals that are labeled
"UTILITY CONNECTION."
6. Connect the utility service neutral to the Transfer Switch
Neutral Terminal.
7. Connect the main distribution panel feeder
conductors to the transfer switch terminals that are
labeled "LOAD CONNECTION."
8. Connect the Neutral Bus to the Transfer Switch Neutral
Terminal.
9. Connect the Ground Bus to the Transfer Switch Ground
("GND") Terminal.
NOTICE Make sure that the grounding electrode
conductor is connected and bonded as specified by federal,
state and local codes, standards and regulations.
10. Connect the feeder conductors from transfer switch
"GENERATOR CONNECTION" terminals to generator
circuit breaker LINE1 and LINE2 terminals. Refer to
Figure 2 for the correct transfer switch connections.
2
11. Connect the conductor from the Transfer Switch Neutral
Terminal to the generator NEUTRAL terminal. Read the
generator control panel labeling for terminal identification.
12. Connect the conductor from the Transfer Switch Ground
("GND") Terminal to the Generator Ground Terminal.
NOTICE If specifically required by federal, state, or local
codes, make sure the generator grounding conductor is
connected.
13. Use a minimum #14 AWG conductors, to connect the
transfer switch "UTILITY 240 VAC" terminals to the
generator's "240 VAC" terminals through the two-pole
connector included with the generator.
14. Use a minimum #18 AWG twisted pair copper or
aluminum conductors for GND and T/R and for +12VDC
a single #18 AWG. Refer to the table below for the
maximum wire length specified by the wire gauge sizes.
WARNING
 Hazardous Voltage - Installing low and high voltage
wire in same conduit could cause electric shock or burns,
resulting in death or serious injury.
• Do not run low and high voltage wire in the same
conduit unless the insulation rating on ALL wiring is
rated for 600V. See NFPA 70 for more information.
 
Maximum Wire Length
1 - 200 ft
(1 - 60 m)
201 - 300 ft
(61 - 91 m)
301 - 500 ft
(92 - 152 m)
Torque Terminal J7 = 2.5 lb-in.
Basic Transfer Switch Controller (Figure 3):
3
Wire Gauge
18
16
14
7