420010312300 MULTICALOR 1500.1 - 1800.1 PR/PR TS
EN
LANDIS & STAEFA, Model LFL1.622 - LFL1.333 OPERATING CYCLE
Ref. Description
t1
Duration Waiting time for confirmation
of air pressure
t2
Preventilation time
t3
Safety time
t4
Pressurizing time
t5
Time for enabling operation of the
main gas valve on minimum capacity
t6
Time for enabling operation of the
main gas valve on maximum capacity
The control box starts the burner
fan, to carry out the prepurging of
the combustion chamber, and
cheks the vent air pressure throu-
gh the air pressure switch. At the
end of prepurging, the ignition
transformer cuts-in and generates
a spark between the electrodes. At
the same time the two gas valves
open (Vs safety valve and Vl working valve). The total safety, in case of missed ignition or casual burner's flame-out, is
granted by a ionisation probe which cuts-in and sets the burner shutdown within the safety time. In case of gas lack or a
major pressure drop, the minimum air pressure switch shuts down the burner.
Remove cover to gain access to the adjusting cams.The cams are to be adjusted through the suitable key provided for.
Description:
CALCULATING THE BURNER CAPACITY
To calculate the burner's capacity in kW, proceed as follows: Check the gas flow rate (in liters) on
the counter and the time of the reading in seconds.
Proceed with the calculation using the following :
Duration
8"
66"(36")
t1
2"
Pressostato gas
Gas manostat
4"
Motore ventilatore
Fan motor
10"
Air Switch
Pressostato aria
Trasformatore
10"
Ignition transformer
di accensione
Valvola gas
Gas valve
Consenso
Min/max capacity
min./max. potenza
enabling device
100%
Serranda aria
min
Air damper
0
Gas damper
Serranda gas
Rivelazione
Flame detector
di fiamma
Cut-out pilot lamp
Spia di blocco
LANDIS & STAEFA SQM 50.481A2 AIR DAMPER MOTOR
I
II - Limit switch for the air damper position at burner's shut down.
III - Ignition flame opening position adjusting cam (Gas).
Cam VIII
IV - Ignition flame opening position adjusting cam(Light-Oil).
is never used
V
VI - Low flame operating opening position adjusting cam (Light-Oil).
VII - Not used cam.
VIII- Not used cam.
Normal operating cycle
Ciclo di funzionamento normale
t2
t3
t4
t5
t6
- High flame operating opening position adjusting cam (
Light-Oil /Gas).
- Low flame operating opening position adjusting cam (Gas).
e x f = kW
sec
20
Operating cycle in the event of
Ciclo di funzionamento
ignition failureNormal operating cycle
in mancanza di fiamma all'accensione
t1
t2
t3
t4
e
= Litres gas
sec = Time in second
G20 = 34,02
f
G30 = 116
G31 = 88